potentially damaging activity, they alert the central
station operator. The data network's communication
link is continuously supervised. Even when monitoring
thousands of control panels, the system consumes
only a small amount of bandwidth.
Certifications and approvals
Region Certification
USA UL AMCX: Central Station Alarm Units
(UL1610 and UL1635); AMCX7: Central
Station Alarm Units Certified for Canada
(cULus)
UL UOJZ: Control Units, System (UL864)
Brazil ANATEL 2025-07-1855
USA CSFM 7300-1615:0232
Installation/configuration notes
The D6100i and Monitoring Centers
The D6100i has extended edges so that installers can
mount it easily into a standard 48.3 cm (19 in.) rack
cabinet. Rack cabinets conserve floor space.
Notice
Rack cabinets are sold separately by a variety of
manufacturers.
The D6100i connects directly to automation
computers. Users can use the automation system or
the D6100i keypad to acknowledge events. There is up
to a 2000 event history buffer.
Network Communications and Control Panels
For network communications, it is necessary to use
one of following modules with the appropriate control
panel: Conettix C900V2 Dialer Capture Ethernet
Module or Conettix DX4020 Ethernet Network
Interface Module.
Review the control panel specifications for the
recommended network interface or dialer capture
modules.
The D6100i can supervise up 10 network accounts
without a D6201 Security Key. To use the full account
capacity, a D6201 Security Key is required.
Parts included
Quantity Component
1 Conettix D6100i Communications Receiver/Gateway
1 P6602 Input and Output Cable
1 Conettix D6200CD CD-ROM
1 External Battery Connection
1 Country Specific AC Transformer (refer to Ordering
Information for details)
Technical specifications
Automation Outputs
Automation Outputs: SIA mode
6500 mode
Enclosure
Rack Mount Dimensions (2U): 9.0 cm. x 37.5 cm x 25.5 cm
(3.5 in. x 19 in. x 10 in.)
Standalone Dimensions: 9.0 cm. x 30.5 cm. x 25.5 cm
(3.5 in. x 12 in. x 10 in.)
Weight : 3 kg (7 lb)
Environmental Considerations
Temperature (Operating): 0°C to 50°C
(+32°F to +122°F)
Power Requirements
AC Nominal Operating Range: 18 VAC ±15% with 50 VA
transformer
Standby Power: Uninterruptible power supply
(UPS) containing a sealed lead-
acid battery, 12 V, 7 Ah to 18 Ah
Current Requirements
Battery Current: 330 mA
UPS AC Standby Current: 180 mA
Telephone
Telephone: RJ11C modular jacks, with
26 AWG or larger wire diameter
Ringer Equivalence Number (REN)
REN: 0.4 B
Industry Canada (IC) REN: 0.2
Display
Screen Dimensions: 1.8 cm x 15.2 cm (0.7 in. x
6.0 in.) dot matrix LCD, 5 x 7
dots per character. Shows two
separate lines, 40 characters per
line.
Indicators: LED display section indicates
receiver status and power.
Inputs and Outputs
For Automation Computer
Connection:
One RS-232 interface port COM3
or Ethernet for IP
For External Serial Printer, PC,
Modem:
One RS-232 interface port COM4
For Parallel Printer Connection: One parallel printer port
Number of Programmable Inputs: Two (wire harness included)
3 | Conettix D6100i Communications Receiver/Gateway