Conettix D6600/D6100 | Computer Interface Manual | 3.0 Computer Communication Protocols
.
Bosch Security Systems, Inc. | 1/07 | 4998122703-01 51
3.2.31 SafeCom (Message Type p)
SIA Mode Description SafeCom
Example
<LF><CRC><p><sequence#><receiver#><line#>[#aaaa|EEEEdata]<CR>
Table 87: SafeCom (Message Type p) Byte Description
Title Description
LF
Standard line feed character.
CRC
Cyclical redundancy check number.
Message
p
sequence#
The message sequence number. The valid sequence number range is 0001 to 9999.
receiver#
The receiver gateway that sent the message. Valid digits: 01 to 99 for D6600.
line#
The line number of the line in the receiver gateway that sent the message. Valid digits: 00 to
99. The receiver uses Line 0 (zero) for internal messages.
account #
The communicator's account number has four digits.
EEEE
Event code, four digits.
data
Event code parameter data.