Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication
Protocols
66
3.2.21 Seriee FSK (Message Type k)
Seriee FSK
Example
SIA Mode Description
<LF><CRC><k><sequence#><receiver#><line#>[#aaaaa|EZZ]<CR>
Table 77: Seriee FSK (Message Type k) Byte Description
Title Description
LF Standard line feed character.
CRC Cyclical redundancy check number.
Message Type k
sequence# The message sequence number. The valid sequence number range is 0001
to 9999.
receiver# The receiver gateway that sent the message. Valid digits are 01 to 99 for
D6600/D6100/D6100IPv6.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the message.
Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal
messages.
Account # The communicator's account number has up to six digits.
E Event code.
ZZ Zone number.